How many amps is my hot water heater?

Ava Scott | 2023-06-07 10:41:45 | page views:1186
I'll answer
Earn 20 gold coins for an accepted answer.20 Earn 20 gold coins for an accepted answer.
40more

Benjamin Davis

Works at the International Seabed Authority, Lives in Kingston, Jamaica.
A water heater of this type is required to be considered a continuous load meaning that the branch circuit needs to be calculated at 125% of the heater's rated ampacity. 4500/240 = 18.75 amps, will work on a 20 amp OCPD but, 18.75*125% = 23.4 amps, requires a 25 or 30 amp circuit.Oct 2, 2012
2023-06-07 10:41:45

William Anderson

QuesHub.com delivers expert answers and knowledge to you.
A water heater of this type is required to be considered a continuous load meaning that the branch circuit needs to be calculated at 125% of the heater's rated ampacity. 4500/240 = 18.75 amps, will work on a 20 amp OCPD but, 18.75*125% = 23.4 amps, requires a 25 or 30 amp circuit.Oct 2, 2012